EAOM-210 FLJ.eng / ver 0.0
Pages 55 / 132
(EXP.CNF.INPUT-2 PAGE) EXPANSION CONFIGURABLE INPUT (2) page
DIS,USERCNF.OR LIST
0- Disable
1- User Configured
2- Select From List
(dis)0 - 2
1
HARDWARE TYPE
Hardware type:
(0 = -Ve, 1 = +Ve)
0 - 1
0
POLARITY
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0 - 1
0
INDICATION
If User Configured
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
0 – 4
0
ACTIVATION
If User Configured
0- Active From Starting
1- Active From Safety On
2- Always Active
0 – 2
2
SELECT FROM LIST
If Select From List
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
1 – 21
2
INPUT TIME DELAY
Input active delay
SEC
0 - 250
5