EAOM-210 FLJ.eng / ver 0.0
Pages 20 / 132
3.2 Programming Procedure
Many of the unit functions can be set by programming. Programming can be
carried out only while the unit is in
OFF
mode. Press the OFF (26) button. If the engine
is running, it will stop and the LED (9) lights on.
The parameters have been divided into groups according to their functions. Every group
has a title and firstly user must determine the title (page) for accessing to the parameters.
Refer to the parameters section for detailed information about parameters.
3.3 Accessing to the Operator Parameters
OPERATOR SECTION
PASSWORD
0
PROG
Operation Screen
Note1:
If Enter button is
pressed and the operator
password is zero, Password
screen is ignored.
OPERATOR PASSWORD
When the prog button is
pressed, password is
asked for accessing to
parameters.
User can access to operator parameters by
entering operator or technician password.
This selection is done with increment and
decrement buttons.
Enter
password with
increment and
decrement
buttons.
Press the Enter button to
confirm password. If the
password is incorrect, the
unit will drop out of
program mode.
Note2:
When Password
message is shown, parameters
can be seen by pressing Enter
button without entering operator
password. But user can not
change the parameters.
Operator and technician
can access to this page.
MAINS LEVELS Page
PROG
OPERATOR SECTION
PROG
OPERATOR SECTION
PASSWORD
161
PROG
OPERATOR SECTION
MAINS LEVELS PAGE
PROG
OPERATOR SECTION
GEN.VOLT.LEVELS PAGE
PROG
Operator or technician can access
to the following page by pressing
increment button
Operator and technician
can access to this page.
Operator or technician can access
to the following page by pressing
increment button
GENERATOR VOLTAGE
LEVELS Page
MAINS & LOAD
L12: 380Vac I1: 126A
Fq:50.0Hz
AUTO
L23: 380Vac I2: 126A
L31: 380Vac I3: 126A
IT: 378A
IEA: 63A
CRANKNG ATTEMP
OVER SPEED PREALARM!