EAOM-210 FLJ.eng / ver 0.0
Pages 19 / 132
Number Comment:
15
This button is used for showing previous working screen in normal operation. In
Programming mode, it operates as an page changing function or decrement function
(decrease value).
16
This button is used for rotating between Event Log screens in normal operation, and
between programming parameters in programming mode.
17
This button closes the mains contactor, only operative when manual mode is selected.
18
This button opens the mains contactor, only operative when manual mode is selected.
19
This button closes the alternator contactor, only operative when manual mode is
selected.
20
This button opens the alternator contactor, only operative when manual mode is
selected.
21
The START button is used for starting the engine when the unit is in the Manual Mode.
22
The STOP button is used for stopping the engine when the unit is in the Manual Mode.
23
The LAMP TEST button illuminates all LED indicators.
24
This button will silence the alarm horn after a failure has been detected.
25
This button will reset the controller after a failure has been detected.
26
The OFF button is used for changing operating mode of the unit to the OFF Mode.
27
The AUTO button is used for changing operating mode of the unit to the AUTO Mode.
28
The TEST button is used for changing operating mode of the unit to the TEST Mode.
29
The MAN button is used for changing operating mode of the unit to the MANUAL Mode.
30
128x64 Dot matrix LCD Display. This is used for displaying the electrical measurements
during normal operation (features explained in section 5.1.1.), and editing/inspecting
programming parameters in program mode.
31