22 REMOTE INHIBIT
In automatic mode, if any of the configurable inputs is congigured as ’16 Auto Start Inhibit’
and this input is active, unit inhibits to work of the generator. In addition to this, if this input is
active while the generator is working, unit stops the generator.
23 TEST ON LOAD
If this input is active when the unit is in test mode, load is transferred to the generator to do
the test on load. If the input is not active, test is done without load.
24 GENERATOR IS SUPPLYING THE LOAD IN OFF MODE
If this input is active when the unit is in OFF mode, the power is calculated. If the input is not
active, the power is not calculated.
25 LOW OIL PRESSURE (FOR CONFIGURABLE INPUT-4)
This input is used as the oil pressure failure input.
25 HIGH TEMPERATURE (FOR CONFIGURABLE INPUT-5)
This input is used as the temperature failure input.