EAOM-210 FLJ.eng / ver 0.0
Pages 11 / 132
1-
2-
Connect the unit as shown in the appropriate diagram. Be sure to connect
the battery supply the right way round and battery negative should be
grounded. The connectors can be unplugged from the rear of the unit to
facilitate connection.
Screened cable must be used for connecting the Magnetic Pickup,
ensuring that the screen is grounded at one end ONLY.
3 The CAN interface requires that a 120 Ohms terminator is fitted to each
end of the communications link. This termination resistor is fitted internally
into the unit. So it is not required externally.
-