Section 8 Specifications & Ratings
Specification:
Description:
Equipment use
Electrical control equipment for generating sets
Housing & Mounting
144 mm x 204 mm x 37 mm. (including connectors) plastic
housing for panel mounting.
Panel Cut-Out
138 mm x 186 mm.
Protection
IP54 at front panel, IP20 at rear side.
Weight
Approximately 0,76 Kg.
Environmental rating
Standard, indoor at an altitude of less then 2000 meters with
non-condensing humidity.
Operating / Storage
Temperature
0°C to +50°C / -25°C to +70°C
Operating / Storage
Humidity
90 % max. (non-condensing)
Installation Over Voltage
Category
II Appliances, portable equipment.
Pollution Degree
II, Normal office or workplace, non conductive pollution
Mode of Operation
Continuous
EN 61000-6-4, EMC Generic Emission Standard for industrial
equipment
EMC
EN 61000-6-2, EMC Generic Immunity Standard for industrial
equipment
Electrical Safety
EN 61010-1, Safety Requirements for electrical equipment for
measurement, control and laboratory use
DC Battery Supply
Voltage
8 to 32 VDC max. operating current is 360 mA.
Cranking Dropouts
Battery voltage can be “0” VDC for max. 100 ms during cranking
(battery voltage should be at least nominal voltage before
cranking).
Battery Voltage
Measurement
8 to 32 VDC, accuracy: 1 % FS, resolution: 0,1 V
Mains Voltage
Measurement
Selectable three phase or single phase, 4 wire connection for
three phase, 2 wire connection for single phase gen-set. 35 to
300 VAC Ph-N, 15.6 to 99.9 Hz. Accuracy: 1 % FS, Resolution: 1 V
Mains Frequency
15.6 to 99.9 Hz (min. 35 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
Generator Voltage
Measurement
Selectable three phase or single phase, 4 wire connection for
three phase, 2 wire connection for single phase gen-set. 35 to
300 VAC Ph-N, 15.6 to 99.9 Hz. Accuracy: 1 % FS, Resolution: 1 V
Generator Speed
From magnetic pick-up: 35 to 10000 Hz (4 to 35 volts peak
continuously.) Accuracy: 0,25 % FS
Generator Frequency
From alternator voltage: 15.6 to 99.9 Hz (min. 35 VAC Ph-N)
Accuracy: 0,25 % FS, Resolution: 0,1 Hz.
CT secondary
5A.
Charge Generator
Excitation
220mA, max 4W.