EAOM-210 FLJ.eng / ver 0.0
Pages 12 / 132
Table 2.1 shows the connections and recommended cable sizes. Table 2.2 describes
the functions of the connections.
Table 2.1 Unit wiring
Pin
Description
Cable Size
(mm²)
Notes
1
Mains voltage input (L1)
2,5
2
Mains voltage input (L2)
2,5
3 phase applications only.
3
Mains voltage input (L3)
2,5
3 phase applications only.
4
Mains voltage neutral
2,5
5
Alternator voltage input (L1)
2,5
6
Alternator voltage input (L2)
2,5
3 phase applications only.
7
Alternator voltage input (L3)
2,5
3 phase applications only.
8
Alternator voltage neutral
2,5
9
Not connected
10 Fuel level sender
1
Connect to fuel level
sender
11 Coolant temperature sender
1
Connect to Coolant
temperature sender
12 Low oil pressure sender
1
Connect to Low oil pressure
sender
13
14
Input from magnetic pick-up
1
Connect to magnetic pick-
up device
15 Input from charge generator
1
NC to “0” volt.
16 Configurable input-6
1
Switch to “B”.
17 High temperature or configurable input-5
1
Switch to “0” volt.
18 Low oil pressure or configurable input-4
1
Switch to “0” volt.
19 Configurable input-3
1
Switch to “0” volt.
20 Configurable input-2
1
Switch to “0” volt.
21 Configurable input-1
1
Switch to “0” volt.
22 Input from emergency stop
1
NC to “0” volt. When the
switch is opened, the
engine is stopped.
23 Mains Contactor Open Relay Output
2,5
24 Mains Contactor Open Relay Output
2,5
25 Mains Contactor Close Relay Output
2,5
26 Mains Contactor Close Relay Output
2,5
27 Gen. Contactor Open Relay Output
2,5
28 Gen. Contactor Open Relay Output
2,5
29 Gen. Contactor Close Relay Output
2,5
30 Gen. Contactor Close Relay Output
2,5
31 Output to fuel / stop solenoid
2,5
16 A. Max.
DC supply from Pin 32
32 +Battery supply input
2,5
Supplies to Pin 31,33,34
33 Output to start
2,5
16 A. Max.
DC supply from Pin 32
34 Horn or configurable relay output-1
2,5
16 A. Max.
DC supply from Pin 32
35 +Battery supply input
2,5
Supplies to Pin 36,37,38
36 Configurable relay output-2
2,5
5 A. Max.
DC supply from Pin 35