EAOM-210 FLJ.eng / ver 0.0
Pages 82 / 132
74 OVERSPEED SHUTDOWN
This output indicates that the over speed shutdown has occurred.
75 PANEL LOCK
This output indicates that the module ‘panel lock’ is active. If the panel lock input is active,
the modul will not respond to operation of the Mode select or start buttons. This allows the
module to be placed into a spesific mode (such as auto) and then secured.
76 PRE-HEAT(during preheat timer)
The output controls the pre-heater. Pre-heat output is available for the duration of pre-heat
timer, which terminates prior to cranking.
77 PRE-HEAT(until end of cranking)
The output controls the pre-heater. As ‘ Pre-heat (during pre-heat timer)’ mode but pre-heat
is also available during cranking.
78 PRE-HEAT(until end of warming)
The output controls the pre-heater. As ‘ Pre-heat (until safety on)’ but pre-heat continues to
be available until the warm-up timer has elapsed.
79 PRE-HEAT(until end safety on)
The output controls the pre-heater. As ‘ Pre-heat (until end of cranking)’ but pre-heat is also
available while waiting for the delayed alarms to become active.
80 REMOTE START PRESENT
This output indicates that a digital input that has been configured as ‘remote start’ is active.
This output could be used to pass the remote start signal on to elsewhere in the control
system.
81 REMOTE STOP DELAY IN PROGRESS
This output source will be active to indicate that the return timer is running.
82 SHORT CIRCUIT
This output indicates that the module has detected a short circuit on the generator output.
83 START RELAY ENERGISED
The output mimics the operation of the start relay. Can be used to control external logic
circuitry.
84 STARTING ALARM
This output is used to supply an external sounder with a signal that the engine is about to
start. The output will be active during the start delay and pre-heat timer (if used).
85 STARTING ALARMS ARMED
The output indicates that the starting alarms are now enabled. It can be used to control
external logic circuitry. Starting alarms are armed as soon as module commences starting of
the engine and remain armed until the engine at rest.
86 STOP BUTTON PRESSED
This output indicates that the stop pushbutton being operated. Once the button is released
the output will become inactive.
87 SYSTEM IN AUTO MODE
The output indicates that the module is in the Auto mode.