25
Reference Manual
00809-0200-4702, Rev CA
Section 3: Mounting, Wiring Switches, and Sensors:
Models 702DX22 and 702DX61
February 2013
Mounting, Wiring Switches, and Sensors:
Models 702DX22 and 702DX61
Figure 3-11. Fuel Sensor wiring
Note
All part numbers on this page refer to products sold by Tyco Thermo Controls, LLC.
The Emerson Smart Wireless 702 transmitter can support up to 500 feet (150 m) of
TraceTek hydrocarbon or solvent sensor cable (TT5000 or TT5001 series). The total
amount of sensor cable connected to a single 702 transmitter is not to exceed 500 ft.
However leader cable, jumper cables (if used) and branch connectors are not included
in the 500 foot limit. See
Figure 3-12
for typical configurations.
Figure 3-12. Fuel Sensor sensor cable wiring
TT-MLC-MC-BLK (Leader Cable)
TT-FFS-100 or TT-FFS-250
(Fast Fuel Sensor Probe)
TT-MLC-MC-BLK (Leader Cable)
TT-FFS-100 or TT-FFS-250
(Fast Fuel Sensor Probe)
TT-ZBC-xx-MC-BLK
(Branch Connector)
TT-MJC-xx-MC-BLK (Optional Jumper Cable)
TT-MLC-MC-BLK (Leader Cable)
TT5000/TT5001 Sensor Cable
(up to 500 ft.)
TT-MET-MC (End Termination)
TT-MJC-xx-MC-BLK (Optional Jumper Cable)
TT-ZBC-xx-MC-BLK
(Branch Connector)
TT-MET-MC
(End Termination)
Up to 500 ft. TT5000 or TT5001
sensor cable
(Total per 702)
TT-MET-MC
(End Termination)