Section 4: Commissioning: Models 702DX22 and 702DX61
February 2013
Commissioning: Models 702DX22 and 702DX61
Figure 4-3. Network Join Status Screens
Connecting with a Field Communicator
A 702 DD is required for HART communication. For connecting with a Field Communicator, refer
to
Figure 2-3 on page 12
.
Checking for Communication Using the Smart Wireless Gateway
In the integrated web interface from the Gateway, navigate to the Explorer page. This page
shows whether the device has joined the network and if it is communicating properly.
NOTE:
The time to join the new device(s) to the network is dependent upon the number of devices
being joined and the number of devices in the current network. For one device joining an
existing network with multiple devices, it may take up to five minutes. It may take up to 60
minutes for multiple new devices to join the existing network.
What to do if there is Immediately an Alarm Present
If the device joins the network and immediately has an alarm present, it is likely due to sensor
configuration. Check the sensor wiring (see
“702 Terminal Block” on page 11
) and the sensor
configuration (see
“Fast Key Sequence” on page 15
).
Searching for
Network
Joining Network
Connected with
Limited
Bandwidth
Connected
Function
Key Sequence
Menu Items
Communications
3,3
Join Status, Communication
Status, Join Mode, Number of
Available Neighbors, Number
of Advertisements Heard,
Number of Join Attempts