11
Reference Manual
00809-0200-4702, Rev CA
Section 2: Configuration: Models 702DX22 and 702DX61
February 2013
Configuration: Models 702DX22 and 702DX61
2.4
Configuring the Device Network
Configuring Device Network with Field Communicator
To communicate with the Gateway, and ultimately the Information System, the transmitter
must be configured to communicate with the wireless network.
Using a Field Communicator or AMS Wireless Configurator, enter the Network ID and Join Key so
they match the Network ID and Join Key of the Gateway and the other devices in the network. If
the Network ID and Join Key are not identical, the transmitter will not communicate with the
network. The Network ID and Join Key may be obtained from the Gateway on the Setup>Net-
work>Settings page on the web server. Using a Field Communicator, the Network ID can be
configured by entering the Fast Key Sequence: 2, 2, 1, 1. The Join Key can also be configured
using a Field Communicator with the Fast Key Sequence: 2, 2, 1, 2.
Configuring Device Network with AMS Wireless Configurator
The final device network configuration piece is the Update Rate which, by default, is 1 minute. It
can be changed at commissioning, or at any time, by using AMS Wireless Configurator or the
Gateway’s web server. The Update Rate should be between 4 seconds and 60 minutes. To
change the Update Rate with a Field Communicator, use the Fast Key Sequence: 2, 2, 1, 3.
If doing a bench top initial configuration, after completion remove the power module until
installation. When the device is installed, insert he power module and close the housing cover
securely. Always ensure a proper seal so that metal touches metal, but do not over tighten.
2.4.1
Configuring Transmitter with Dry Contact Inputs,
Measurement Option Code 22 (702DX22)
Figure 2-1. 702 Terminal Block
Connect the HART communication leads to the COMM terminals on the terminal block.
1
2
4
3