102
Reference Manual
00809-0200-4702, Rev CA
Section 9: Operation and Maintenance: Models 702DX32 and 702DX42
February 2013
Operation and Maintenance: Models
702DX32 and 702DX42
9.5.4
Device diagnostic screens
The following screens will show the device diagnostics depending on the state of the device,
continuing after Diagnostic Button Screen 5.
Diagnostic Button Screen 6.1:
There is a critical error which may
prevent the electronics board
from operating correctly.
Diagnostic Button Screen 6.2:
There is a warning which should
be addressed, but should not
affect the device output.
Diagnostic Button Screen 7.1: the
terminal voltage has dropped
below level of operating limit.
Replace the Black Power Module
model number 701PBKKF
(Part Number:
00753-9220-0001)
Diagnostic Button Screen 7.2: the
terminal voltage is below the
recommended operating range -
if this is a self-operated device,
the power module should be
replaced - for line powered
devices, the supply voltage
should be increased
B o a r d
f a i l u r
B o a r d
w A R N
s u p l y
f a i l u r
s u p l y
l o w