116
Reference Manual
00809-0200-4702, Rev CA
Appendix B: Product Certifications
February 2013
Product Certifications
B.0.6
Hazardous Locations Certificates
North American Certifications
FM Approvals
I5
FM Approvals Intrinsically Safe, Non-Incendive and Dust Ignition-proof
Certificate Number: 3031506
Applicable Standards: Class 3600, 1998; Class 3610, 2010; Class 3611, 2004; Class 3810,
2005; ANSI/NEMA 250
Marking: IS CL I,II,III, DIV 1, GP A, B, C, D, E, F, G.
NI CL I, DIV 2, GP A, B, C, D.
IS CL I, Zone 0, AEx ia llC
T4 Ta =-50 to 70°C
DIP CL II/III, DIV 1, GP E, F, G, AMB TEMP LIMITS -50 TO 85°C
WHEN INSTALLED PER ROSEMOUNT DWG 00702-1000.
FOR USE WITH EMERSON SMARTPOWER OPTION 701PBKKF
WARNING – POTENTIAL ELECTROSTATIC CHARGING HAZARD – SEE INSTRUCTIONS
ENCLOSURE TYPE 4X
IP66 / 67
Special Conditions of Certification:
1.
The Model 702 transmitter housing contains aluminum and is considered a potential
risk of ignition by impact or friction. Care must be taken into account during installation
and use to prevent impact and friction.
2.
The surface resistivity of the polymeric antenna is greater than 1 G
. To avoid
electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry
cloth.
3.
For use only with the Model 701P or Rosemount 753-9220-XXXX Smart Power Battery
Module.
N5
FM Approvals Non-Incendive and Dust Ignition-proof
Certificate Number: 3031506
Applicable Standards: Class 3600, 1998; Class 3611, 2004; Class 3810, 2005; ANSI/NEMA
250
Marking: NI CL I, DIV 2, GP A, B, C, D.
T4 Ta =-50 to 70°C
DIP CL II/III, DIV 1, GP E, F, G, AMB TEMP LIMITS -50 TO 85°C
WHEN INSTALLED PER ROSEMOUNT DWG 00702-1000.
FOR USE WITH EMERSON SMART POWEROPTION 701PBKKF
WARNING – POTENTIAL ELECTROSTATIC CHARGING HAZARD – SEE INSTRUCTIONS
ENCLOSURE TYPE 4X
IP66 / 67
Special Conditions of Certification:
1.
For use only with the Model 701P or Rosemount 753-9220-XXXX Smart Power Battery
Module.