Appendix F: Programming the 3102 and 3105 using HART
February 2015
Programming the 3102 and 3105 using HART
Field Communicator or AMS Device
Manager
To view or change the lower range value
1.
From the
Home
screen, select 2: Configure.
2.
Select 2: Manual Setup.
3.
Select 1: Basic Setup.
4.
Select 4: Lower Range Value P016.
5.
If a change is required:
(a) Input a new value, and then select “ENTER” to save it.
(b) Select “Send” or “Apply” to update the transmitter.
Note
When messages appear, take appropriate action if needed and select “OK”.
Rosemount 3490 Series Control Unit
To view or change the lower range value
1.
From the
Main Menu
screen, select SETUP.
2.
Select the transmitter (e.g. “Tx1: 3102”).
3.
Select OUTPUT.
4.
Select CURRENT.
5.
Select Low Range Val.
6.
Follow the on-screen instructions to input and save the new setting.
(Use the Enter (
) key if prompted to change mode to “off-line”).
7.
Select “Quit” to exit to the previous menu.
Lower Range Value P016
0 ft
0
ESC
DEL
ENTER
HELP
w
s
q
a
z
Lock
Shift
@ &
á ü
x
e
d
c
r
f
v
t
g
b
y
h
n
u
j
m
*
-
+
/
.
0
7
4
1
8
5
2
9
6
3
i
k
o
l
FN
(
Field Communicator Screen Shown
)
Low Range Val P016
0.000ft
Esc=Quit =Edit
(
Rosemount 3491 Screen Shown
)
Summary of Contents for Rosemount 3101
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4840 Rev CB Title Page February 2015 ...
Page 12: ...x Reference Manual 00809 0100 4840 Rev CB Contents February 2015 Contents ...
Page 34: ...22 Reference Manual 00809 0100 4840 Rev CB Section 3 Installation February 2015 Installation ...
Page 68: ...56 Reference Manual 00809 0100 4840 Rev CB Section 4 Starting up February 2015 Starting up ...
Page 236: ...224 Reference Manual 00809 0100 4840 Rev CB Index February 2015 Index ...
Page 237: ......
Page 238: ......
Page 239: ......