Reference Manual
00809-0100-4840, Rev CB
Appendix F: Programming the 3102 and 3105 using HART
February 2015
Programming the 3102 and 3105 using HART
F.4.5
% of current output (D905)
This indicates the percentage of the 4–20 mA output current in use.
0% represents 4 mA
100% represents 20 mA
Note
When the Poll Address (
) is a non-zero number, the transmitter is in
multi-drop mode
and the current output is fixed at 4 mA. However, the read-only parameter D905 remains active.
Field Communicator or AMS Device
Manager
To view the percentage of current output
in use
1.
From the
Home
screen, select 3: Service Tools.
2.
Select 2: Variables.
3.
Select 2: Analog Output.
4.
Select 3: Percentage of Current Output.
5.
When finished, use the Bksp key to exit to the previous menu.
Rosemount 3490 Series Control Unit
To view the percentage of current output
in use
1.
From the
Main Menu
screen, select MONITOR.
2.
Select the transmitter (e.g. “Tx1: 3102”).
3.
Select READINGS, and then select CURRENT.
4.
Select % of Current Output.
5.
When finished, use the ESC key to exit to the previous menu.
Fast Keys
3, 2, 2, 3
Percentage Current Output - (%)
Value: 90.039
HELP
0
100
75
50
25
(
Field Communicator Screen Shown
)
% Current Out D905
90.0%
(
Rosemount 3491 Screen Shown
)
Summary of Contents for Rosemount 3101
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4840 Rev CB Title Page February 2015 ...
Page 12: ...x Reference Manual 00809 0100 4840 Rev CB Contents February 2015 Contents ...
Page 34: ...22 Reference Manual 00809 0100 4840 Rev CB Section 3 Installation February 2015 Installation ...
Page 68: ...56 Reference Manual 00809 0100 4840 Rev CB Section 4 Starting up February 2015 Starting up ...
Page 236: ...224 Reference Manual 00809 0100 4840 Rev CB Index February 2015 Index ...
Page 237: ......
Page 238: ......
Page 239: ......