Appendix F: Programming the 3102 and 3105 using HART
February 2015
Programming the 3102 and 3105 using HART
F.3.45
Minimum temperature (P047)
This is a record of the lowest measured temperature inside the transmitter.
Field Communicator or AMS Device
Manager
To view the minimum temperature
1.
From the
Home
screen, select 2: Configure.
2.
Select 2: Manual Setup.
3.
Select 8: Set Temperature (
3105
) or
9: Set Temperature (
3102
).
4.
Select 3: Internal Extremes.
5.
Select 4: Minimum Temperature P047.
Rosemount 3490 Series Control Unit
To view the minimum temperature
1.
From the
Main Menu
screen, select MONITOR.
2.
Select the transmitter (e.g. “Tx1: 3102”).
3.
Select DIAGNOSTICS.
4.
Select HISTORY.
5.
Select Min Temp.
6.
When finished, select EXIT to exit to the previous menu.
Fast Keys
2, 2, 8 [or 9], 3. 4
Minimum Temperature P047
-11 degC
-11
ESC
DEL
ENTER
HELP
w
s
q
a
z
Lock
Shift
@ &
á ü
x
e
d
c
r
f
v
t
g
b
y
h
n
u
j
m
*
-
+
/
.
0
7
4
1
8
5
2
9
6
3
i
k
o
l
FN
(
Field Communicator Screen Shown
)
Min Temp P047
-11
°
C
(
Rosemount 3491 Screen Shown
)
Summary of Contents for Rosemount 3101
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4840 Rev CB Title Page February 2015 ...
Page 12: ...x Reference Manual 00809 0100 4840 Rev CB Contents February 2015 Contents ...
Page 34: ...22 Reference Manual 00809 0100 4840 Rev CB Section 3 Installation February 2015 Installation ...
Page 68: ...56 Reference Manual 00809 0100 4840 Rev CB Section 4 Starting up February 2015 Starting up ...
Page 236: ...224 Reference Manual 00809 0100 4840 Rev CB Index February 2015 Index ...
Page 237: ......
Page 238: ......
Page 239: ......