background image

® U.S. Registered Trademark
Copyright © 1996 Honeywell Inc.  •   All Rights Reserved

X-XX UL

INSTALLATION INSTRUCTIONS

AT150F, AT175F

Universal Circuit Breaker Transformers

APPLICATION

These transformers provide power to 24 Vac circuits in heating/cooling control systems. Although the transformers are
typically used in heating/cooling control systems, they can be used in any application that does not exceed the load
ratings. They include a button for manually resetting the circuit breaker. They meet National Electrical Code Class 2 “not
wet” and Class 3 “wet” requirements and are Underwriters Laboratories (UL) Inc. listed under UL 1585. Transformers can
be foot-mounted or conduit/panel mounted. See Table 1 for additional specifications.

Table 1. Model Specifications.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazard-
ous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

CAUTION

Disconnect power supply before beginning
installation to prevent electrical shock or equipment
damage.

The transformer can be foot-mounted or conduit/panel
mounted.

Mounting

Foot Mounting

Mount the transformer using screws (not included) through
the four 3/16 in. x 3/8 in. holes in the mounting feet. See
Fig. 1. Make line voltage primary connections within an
approved enclosure.

Fig. 1. Foot mounting.

P r i m a r y

Secondary

Voltage

Output Rating

Model

Number

Input Voltage

(60 Hz)

Wiring  

Connections

Open

Circuit

At Rated Power

Output

Wiring

Connections

 at 100 Percent

  

Power Factor

AT150F

120/208/240

9 in. leadwires

27.0

24.0

9 in. leadwires

50 VA

208/277/480

AT175F

120/208/240

9 in. leadwires

27.0

24.0

9 in. leadwires

75 VA

208/277/480

69-1014-1

USE SCREWS OR 
BOLTS THROUGH
SLOTS (4) IN
MOUNTING FEET

RESET
BUTTON

MOUNTING 
FOOT (2)

LEADWIRES 
FOR PRIMARY 
AND SECONDARY
CONNECTIONS

M6905

Reviews: