the drip loop so the bottom is lower than the conduit connections and the
transmitter housing.
4.6.2
Grounding the transmitter
Signal cable shield grounding
Signal cable shield grounding is summarized in
and
. The signal cable
shield and unused shield drain wire must be trimmed and insulated, ensuring that the
signal cable shield and drain wire do not come in contact with the transmitter case. See
for instructions on grounding the transmitter case. Follow the
steps below to correctly ground the signal cable shield.
Do not run signal wiring in conduit or open trays with power wiring, or near heavy
electrical equipment. Grounding terminations are provided on the outside of the
electronics housing and inside the terminal compartment. Use these grounds when
transient protect terminal blocks are installed or to fulfill local regulations.
Procedure
1. Remove the field terminals housing cover.
2. Connect the wiring pair and ground as indicated in
a) Trim the cable shield as short as practical and insulate from touching the
transmitter housing.
Note
Do NOT ground the cable shield at the transmitter; if the cable shield touches
the transmitter housing, it can create ground loops and interfere with
communications.
3. Continuously connect the cable shields to the power supply ground.
a) Connect the cable shields for the entire segment to a single good earth
ground at the power supply.
Note
Improper grounding is the most frequent cause of poor segment
communications.
4. Replace the housing cover.
Emerson recommends tightening the cover until there is no gap between the cover
and the housing.
5. Plug and seal unused conduit connections.
Transmitter case grounding
Always ground the transmitter case in accordance with national and local electrical codes.
The most effective transmitter case grounding method is a direct connection to earth
ground with minimal impedance. Methods for grounding the transmitter case include:
•
Internal ground connection: The internal ground connection screw is inside the FIELD
TERMINALS side of the electronics housing. This screw is identified by a ground symbol
Reference Manual
Electrical installation
00809-0100-4774
July 2020
Reference Manual
89
Summary of Contents for Rosemount 3051 CF Series
Page 4: ...4 ...
Page 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Page 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Page 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Page 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Page 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Page 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...