7. Set damping: PRIMARY_VALUE_DAMPING.
8. Set up LCD display.
9. Review transmitter configuration.
10. Set switches and software write lock.
Prerequisites
to graphically view the step by step process for basic device configuration.
Before beginning configuration, you may need to verify the device tag or deactivate
hardware and software write protection on the transmitter. To do this, follow the steps
below. Otherwise continue at
.
1. To verify the device tag:
a. Navigation: from the
Overview
screen, select
Device Information
to verify the
device tag.
2. To check the switches (see
):
a. The
Write Lock
switch must be in the unlocked position if the switch has
been enabled in software.
b. To disable the software write lock (devices ship from the factory with the
software write lock disabled):
•
From the
Overview
screen, select
Device Information
and then select the
Security and Simulation
tab.
•
Perform
Write Lock Setup
to disable software write lock.
Note
Place the control loop in Manual mode before beginning analog input block configuration.
Note
Always check and reconcile function block configuration (with the exception of resource
and transducer blocks) after commissioning the transmitter to the control host. You may
not save function block configuration, including AI blocks, made prior to device
commissioning to the control host to the control host database during the commissioning
process. In addition, the control host may download configuration changes to the
transmitter as part of the commissioning process.
Note
Typically, make changes to the AI block configuration after the transmitter is
commissioned using the control host configuration software. Consult your host system
documentation to see if the AI Block guided configuration method provided in the DD or
DTM should be used after the device has been commissioned.
Note
For DeltaV users, only make final AI block configuration and AI block configuration
changes using the DeltaV Explorer.
Procedure
1. Begin configuring the AI block.
Reference Manual
Configuration
00809-0100-4774
July 2020
Reference Manual
35
Summary of Contents for Rosemount 3051 CF Series
Page 4: ...4 ...
Page 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Page 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Page 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Page 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Page 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Page 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...