3.5.4
Inline process connection
Inline gage transmitter orientation
CAUTION
Erroneous pressure values
The transmitter may output erroneous pressure values.
Do not interfere or block the atmospheric reference port.
The low side pressure port on the inline gage transmitter is located in the neck of the
transmitter, behind the housing. The vent path is 360 degrees around the transmitter
between the housing and sensor (see
).
Keep the vent path free of any obstruction, such as paint, dust, and lubrication, by
mounting the transmitter so that the process can drain away.
Figure 3-11: Inline Gage Low Side Pressure Port
A
A. Low side pressure port (atmospheric reference)
CAUTION
Electronics damage
Rotation between the sensor module and the process connection can damage the
electronics.
Do not apply torque directly to the sensor module.
To avoid damage, apply torque only to the hex-shaped process connection.
Hardware installation
Reference Manual
July 2020
00809-0100-4774
70
Rosemount 3051
Summary of Contents for Rosemount 3051 CF Series
Page 4: ...4 ...
Page 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Page 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Page 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Page 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Page 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Page 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...