7
Advanced pressure diagnostics
7.1
Overview
The Rosemount 3051S F
OUNDATION
™
Fieldbus Pressure Transmitter with Advanced
Diagnostics Suite is an extension of the Rosemount 3051S Scalable
™
Pressure Transmitter
and takes full advantage of the architecture. The Rosemount 3051S SuperModule
™
Platform generates the pressure measurement. The FOUNDATION Fieldbus Feature Board
is mounted in the Plantweb
™
housing and plugs into the top of the SuperModule.
The Advanced Diagnostics Suite is an order option on the F
OUNDATION
Fieldbus feature
board, and designated by the option code “D01” in the model number. The Advanced
Diagnostics Suite has two distinct diagnostic functions, Process intelligence and Plugged
Impulse Line Detection (PIL), which can be used separately or in conjunction with each
other to detect and alert users to conditions that were previously undetectable, or provide
powerful troubleshooting tools.
illustrates an overview of these two functions
within the Fieldbus Advanced Diagnostics Transducer Block.
Figure 7-1: Advanced Diagnostics Transducer Block Overview
A
B
C
D
E
F
A. Pressure measurement
B. Plugged impulse line detection
C. Preocess intelligence
D. Plugged impulse line alert
E. Process intelligence alert
F. Statistical parameters
7.2
Process Intelligence
The Advanced Diagnostics Suite features Process Intelligence technology to detect
changes in the process, process equipment or installation conditions of the transmitter.
This is done by modeling the process noise signature (using the statistical values of mean
and standard deviation) under normal conditions and then comparing the baseline values
to current values over time. If a significant change in the current values is detected, the
Reference Manual
Advanced pressure diagnostics
00809-0100-4774
July 2020
Reference Manual
119
Summary of Contents for Rosemount 3051 CF Series
Page 4: ...4 ...
Page 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Page 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Page 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Page 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Page 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Page 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...