An automated task procedure called a
Method
guides you through SPM setup. The basic
sequence of steps is:
Procedure
1. Enter the monitoring cycle.
The minimum monitoring time is one minute; three minutes is a typical monitoring
cycle.
2. For Bypass Verification, select Yes or No. Emerson
™
recommends verification for
applications where SPM monitoring has not been done previously, or where process
changes may cause significant changes in mean or standard deviation.
3. Enter the thresholds in percent.
a) The first threshold is the Mean Change that will trigger an alert.
b) The second threshold is the High Variation Limit that will trigger an alert.
Typical values are from 40–80 percent.
c) The third threshold is the Low Dynamics Limit that will trigger an alert.
d) Filtering is selected or disabled.
4. Enable software write lock.
Example
Note
To enable or disable monitoring or make configuration changes, you may prefer the
manual
SPM Configuration
screen.
Menu navigation:
Configure
→
Manual Setup
→
Basic SPM
Figure 2-23: Configure SPM Display Screen
Reference Manual
Configuration
00809-0100-4774
July 2020
Reference Manual
53
Summary of Contents for Rosemount 3051 CF Series
Page 4: ...4 ...
Page 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Page 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Page 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Page 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Page 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Page 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...