Figure 4-1: Simulate and Security Switches
C
A
B
D
E
F
A. Simulate disabled position
B. Simulate switch
C. Simulate enabled position (default)
D. Security locked position
E. Security switch
F. Security unlocked position (default)
4.4.1
Setting Security switch
Set
Simulate
and
Security
switch configuration before installation as shown in
.
•
The
Simulate
switch enables or disables simulated alerts and simulated AI Block status
and values. The default
Simulate
switch position is enabled.
•
The
Security
switch allows (unlocked symbol) or prevents (locked symbol) any
configuration of the transmitter.
—
Default security is off (unlocked symbol).
—
The
Security
switch can be enabled or disabled in software.
Use the following procedure to change the switch configuration:
Procedure
1. If the transmitter is installed, secure the loop and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the
instrument cover in explosive atmospheres when the circuit is live.
3. Slide the
Security
and
Simulate
switches into the preferred position.
4. Reattach transmitter housing cover; Emerson recommends tightening the cover
until there is no gap between the cover and housing to comply with explosion proof
requirements.
4.4.2
Setting Simulate switch
The
Simulate
switch is located on the electronics. It is used in conjunction with the
transmitter simulate software to simulate process variables and/or alerts and alarms. To
Reference Manual
Electrical installation
00809-0100-4774
July 2020
Reference Manual
85
Summary of Contents for Rosemount 3051 CF Series
Page 4: ...4 ...
Page 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Page 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Page 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Page 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Page 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Page 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...