74
Reference Manual
00809-0100-2460, Rev DE
October 2018
In the tank database of the Rosemount 2410 Tank hub, the Rosemount 2240S temperature transmitter
and the Rosemount 2230 display are grouped into an Auxiliary Tank Device (ATD). The ATD Modbus
address has to be stored in the Temperature Device address field in the tank database of the Rosemount
2460 System Hub as illustrated in
. The Modbus addresses of the level devices must
also be stored in both the 2410 and the 2460 tank databases.
Figure 4-6. The Tank Database of the Rosemount 2460 System Hub must match the tank databases of connected
Rosemount 2410 Tank Hubs
Note that in this example a single Rosemount 2410 Tank Hub serves three tanks. The tanks are mapped
to tank position 1, 2, and 3 in the Rosemount 2410 Tank Hub’s tank database.
In the tank database of the Rosemount 2460 System Hub, you will have to configure 2410 Tank Position in
order to be able to configure the correct Temperature Device Addresses for the three tanks.
Rosemount 2460 System Hub
Tank Database for a Rosemount 2410 Tank Hub that serves three tanks
Level device address
Auxiliary Tank Device (ATD) address
Summary of Contents for Rosemount 2460
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Page 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Page 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Page 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Page 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Page 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Page 239: ......