195
October 2018
Reference Manual
00809-0100-2460, Rev DE
4864-4991
Relay Status
DWORD
Bitfield
Priority 4 question
Bit 0 - 9 (Relay1 - Relay10)
(0 = Not energized, 1 = Energized)
Bit 10 - 19 (Relay1 - Relay10)
(0 = OK or Disabled, 1 = Error)
Bit 20 - 29 (Relay1 - Relay10)
(0 = Used, 1 = Disabled)
Bit 30 Invalid Status
(2460 set to 1 if old status or cfail)
Bit 31 Cfail
(2460 set to 1 if sub device does not
answer, bit 10-19 will also be set to 1)
4992-5119
Safety Relay Status
DWORD
Bitfield
Priority 4 question
Bit 0 (Relay1)
(0 = Not energized, 1 = Energized)
Bit 10 (Relay1)
(0 = OK or Disabled, 1 = Error)
Bit 20 (Relay1)
(0 = Used, 1 = Disabled)
Bit 30 Invalid Status
(2460 set to 1 if old status or cfail)
Bit 31 Cfail
(2460 set to 1 if sub device does not
answer, bit 10 will also be set to 1)
Unit Register Area
9344-9407
User Defined 1 Unit
WORD
Priority 5 question.
This register will define the unit for the
User Defined 1 value above. The unit can
be one of the following:
Level Unit
Temperature Unit
Pressure Unit
Density Unit
Flow Rate Unit
39 = mA
57 = Percent %
No unit
9408-9471
User Defined 2 Unit
WORD
9472-9535
User Defined 3 Unit
WORD
9536-9599
User Defined 4 Unit
WORD
9600-9663
User Defined 5 Unit
WORD
Register
Number
Register Name
Type
Unit
Description
Summary of Contents for Rosemount 2460
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Page 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Page 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Page 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Page 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Page 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Page 239: ......