4.3.3
Preconditions for redundancy setup
The following conditions must be met to allow setting up two Rosemount 2460 System Hubs for
redundancy operation:
The same firmware version on both System Hubs
Firmware version 1.C0 or higher
Rosemount TankMaster version 6.D0 or higher
No warnings or errors
License;
- the same maximum number of tanks
- redundancy option enabled on both system hubs
-
the same number of Modbus TCP clients
The same modem board setup
(1)
(number of boards, modem type, and modem locations)
Hardware write protection disabled
Software write protection disabled
Basically all model codes except Housing, Cable/Conduit Connections, and Options need to be identical for
the Primary and Backup system hubs.
1.
Modem boards supported for redundancy : TRL2 Modbus, RS485, Enraf BPM