50
Reference Manual
00809-0100-2460, Rev DE
October 2018
4.3
Setting up a Rosemount 2460 System Hub
4.3.1
Introduction
A Rosemount 2460 System Hub is easy to install and configure by using the TankMaster Winsetup
configuration program. The WinSetup installation wizard guides you through the basic configuration to
start up a Rosemount 2460.
Host communication via the Ethernet 1 port (ETH1) and Modbus TCP protocol can be setup by using the
Web based Graphical User Interface (GUI). See
Section 6: Service and Troubleshooting
for more
information.
4.3.2
Installation procedure
Installation of a Rosemount 2460 System Hub in a Rosemount Tank Gauging system includes the
following basic steps:
1. Ensure that a plan is available for all tanks and devices with tag names, communication addresses,
number of temperature elements and other data that is needed for a system setup.
2. In case devices from other vendors will be connected to the field ports, ensure that appropriate
modem cards are installed which support the communication protocols. Also, check that the 2460
firmware supports the modem cards and protocols, see
for more information.
TankMaster 6.C0 and higher is required for configuration of 2460 with Enraf
®
support. See
Appendix A: Specifications and Reference Data
for information on supported electrical interfaces and
protocols. See also
“Exchanging a modem card” on page 108
3. Make sure that the Rosemount 2460 is properly wired and up and running. Check that the Power LED
is on and the Status LED indicates normal operation (see
4. (Redundancy). Make sure that the two system hubs are properly wired as described in
. See also
. Note that configuration of redundant Rosemount 2460 is
supported by TankMaster 6.D0 and higher versions.
5. Ensure that the TankMaster WinSetup configuration program is up and running.
6. In WinSetup, setup the appropriate protocol channel
(1)
in the TankMaster host PC. This step will ensure
that communication between the TankMaster PC and the Rosemount 2460 is established.
7. In TankMaster WinSetup, start the device
installation wizard
and configure the system hub as
described in
“Installation wizard” on page 55
:
a. Specify device type (2460) and name tag.
b. Check that the correct communication channel is enabled and verify communication with the
TankMaster host computer.
c. Verify that the Host ports and Field ports are using the right protocols for communication with
TankMaster work stations or other host systems, and with field devices such as the Rosemount
2410 Tank Hub and the Rosemount 5900S Radar Level Gauge.
d. Configure the tank database. See configuration examples that illustrate how the tank databases
of the Rosemount 2460 and the Rosemount 2410 are related to each other in
the Rosemount 2460 System Hub and the Rosemount 2410 Tank Hub” on page 70
.
Configuration of Enraf devices is covered by section
“Enraf® Device Configuration” on page 171
Configuration of Whessoe WM550/660 devices is described in
“Whessoe Device Configuration”
1.
See Section 5 in the
Rosemount System Configuration Manual
(Document no. 00809-0300-5100) for more information on how to configure com-
munication protocol channels.
Summary of Contents for Rosemount 2460
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Page 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Page 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Page 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Page 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Page 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Page 239: ......