221
October 2018
Reference Manual
00809-0100-2460, Rev DE
J.3
Host port configuration
The Configuration window lets you setup communication ports for Enraf 858 CIU emulation.
1. In the TankMaster Winsetup workspace, click the right mouse button on the Rosemount 2460 icon.
2. Select
Properties
to open the system hub’s configuration window.
3. Identify the port that is used for the Enraf CIU 858 emulation.
4. In case port 5 or 6 is used for Enraf CIU 858 communication, verify that protocol type is
HostPort
. If
not, select
Host Port
from the drop-down list.
5. Verify correct Protocol and communication settings. Click the
Advanced
button if you need to
change any communication settings. Note that Ports 5 and 6 can be used as either field or host ports.
Ports 7 and 8 can be used as Host Ports only.
In the default setup, ports 1 - 6 are are configured as field ports. Note that only port 7 can be used for
RS232 communication with the Enraf host.
Summary of Contents for Rosemount 2460
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Page 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Page 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Page 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Page 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Page 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Page 239: ......