192
October 2018
Reference Manual
00809-0100-2460, Rev DE
User Defined Register Area
Priority 3 question
2560-2687
User Defined 1 Value
FLOAT
Unit is specified in Unit Register Area
below, see register 9344-9663.
Status is specified in Status Register
Area, see register 4224-4351.
2688-2815
User Defined 2 Value
FLOAT
2816-2943
User Defined 3 Value
FLOAT
2944-3071
User Defined 4 Value
FLOAT
3072-3099
User Defined 5 Value
FLOAT
Status Register Area
3968-4095
Standard Status
DWORD
Bitfield
Priority 1 question
Bit 0: Simulated Level
Bit 1: Manual Level
Bit 2: Invalid Level
Bit 3: CFail Level
Bit 4: MI Approved Level
Bit 5: MI Legal Level
Bit 6: Backup Level used
Bit 7: Spare
Bit 8: Simulated FWL
Bit 9: Manual FWL
Bit 10: Invalid FWL
Bit 11: CFail FWL
Bit 12: Reserved
Bit 13: Reserved
Bit 14: Backup FWL used
Bit 15: Spare
Bit 16: Simulated Product Temp
Bit 17: Manual Product Temp
Bit 18: Invalid Product Temp
Bit 19: CFail Product Temp
Bit 20: MI Approved Product Temp
Bit 21: MI Legal Product Temp
Bit 22: Backup Product Temp used
Bit 23: Spare
Bit 24: Simulated Vapor Temp
Bit 25: Manual Vapor Temp
Bit 26: Invalid Vapor Temp
Bit 27: CFail Vapor Temp
Bit 28: MI Approved Vapor Temp
Bit 29: MI Legal Vapor Temp
Bit 30: Backup Vapor Temp used
Bit 31: Spare
Register
Number
Register Name
Type
Unit
Description
Summary of Contents for Rosemount 2460
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Page 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Page 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Page 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Page 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Page 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Page 239: ......