136
Reference Manual
00809-0100-2460, Rev DE
October 2018
6.19.2
Firmware upgrade of redundant system hubs
Firmware upgrade of redundant system hubs requires a temporary change to standalone mode.
1. Disable the redundancy function.
a. Use Web Graphical User Interface (GUI) to verify that the Primary device is active, if not do a
manual switch over.
b. Use Web GUI to unpair the redundant pair of system hubs.
c. Primary and Backup device will change mode to Standalone.
d. The Primary will continue to poll field data.
e. The Backup will start using default configuration database (CDB) and default Modbus address.
2. Update firmware on both devices according to normal procedure for a Standalone system as
described in
“Firmware upgrade” on page 135
a. Connect to the service port ETH3.
b. Use WebGUI to upgrade the firmware.
Note
The Host will lose field data when the device that is polling field data is updated with new firmware.
3. Enable the redundancy function again.
a. Connect to the Primary device (this is the unit that has the configured database (CDB) and polls
data from the field devices)
b. Use Web GUI to pair the redundant system hubs.
c. Primary will be the Active device and continue to poll field data.
Summary of Contents for Rosemount 2460
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Page 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Page 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Page 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Page 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Page 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Page 239: ......