User Manual
Chapter 3
GFK-2843A
Jan 2020
VersaPoint potential and data routing, and VersaPoint connectors
21
Table 7: Terminal point assignment for connector 4
Terminal point Signal
Channel assignment
LED
7.1
OUT3_Ch1
Output 3, channel 1
3.1
8.1
OUT3_Ch2
Output 3, channel 2
3.2
7.2
Not used
8.2
Not used
7.3
0 V (GND)
Channel 1 and channel 2
8.3
0 V (GND)
Channel 1 and channel 2
7.4
FE
8.4
FE
WARNING
Loss of functional safety due to parasitic voltages
Connect the ground of the actuator to the ground terminal point of the corresponding
output on the VersaPoint connector. An external ground may not be used.