User Manual
Appendix B
GFK-2843A
Jan 2020
checklists
97
B-1.2
Configuration and parameterization
Checklist for configuration and parameterization of the VersaSafe system
Equipment identification
Date
Author
Test engineer
Remark
No
.
Requirement (mandatory)
Yes
Remark
1 Has the safety logic been configured?
2 Have all inputs and outputs been fully and correctly parameterized?
3 Are standard input signals exclusively used to configure standard
operations (e.g., for the enable principle using the EN_OUT block or for
acknowledgment)?
4 Has it been ensured that in the overall system consisting of VersaSafe
and any higher-level PROFIsafe system, the addresses (address within
the VersaSafe system and F-Address of the PROFIsafe system) are
unique?
5 Has watchdog time t
FWD
been set for each satellite according to the
application?
6 Has the correct terminal point been assigned to the correct signal?
7 Is the island address set correctly?
8 For IC220SDL963 outputs that are parameterized for two-channel
operation, are both channels parameterized correctly for each other?
9 For satellite inputs that are parameterized for two-channel operation,
are both channels parameterized correctly for each other?
10 For satellite outputs that are parameterized for two-channel operation,
are both channels parameterized correctly for each other?
11 Has the switch-off delay for stop category 1 been observed in the
calculation of the total response time for the machine/system?
12 Has prevention of undesired startup/restart been configured?
13 Has it been ensured that an operator acknowledgment can only be
executed by
an intentional user action? (Not configured as “automatic”.)
14 Has the checklist/project information been processed in VersaConf
Safety
(“Project... Project Info” menu item)?
No
.
Requirement (optional)
Yes No Remark
15
Date
Signature (author)
Date
Signature (test engineer)