User Manual
Chapter 7
GFK-2843A
Jan 2020
Startup and validation
47
Step
Relevant section and literature
Once the operating voltage has been applied:
•
If possible, measure the wave form of the
voltages to ensure that there are no
deviations.
•
Measure the output voltages on the
module, as well as the supply voltages,
which supply connected loads (e.g.,
motor) to ensure that they are in the
permissible range.
•
Use the LEDs on the devices to check that
the module starts up without any errors
(there must be no red LEDs permanently
on; the FS LED flashes because the de-
vice is not parameterized).
Check the assembly and installation.
Checklist "Assembly, removal, and electrical
installation" on page 22
Implement data flow between the standard
control system and the safety modules and
between the safety modules themselves.
"IC220SDL963 system handling in various control
systems" on page 80
Download the parameterization and
configuration data from the standard control
system to the safety modules.
"Downloading the configuration and parameter data
record" on page 85
Perform a function test and validation. Check
whether the safety function responds as
planned during configuration and
parameterization.
Checklist "Validation" on page 99
When connecting the supply voltages, use the diagnostic and status indicators to check
whether the module has started up correctly or whether any errors are indicated. For
instructions on how to proceed in the event of an error, please refer to "Errors: messages
and removal" on page 50.