User Manual
Chapter 10
GFK-2843A
Jan 2020
Technical data and ordering data
58
Chapter 10:
Technical data and ordering data
10.1
System data
10.1.1
VersaPoint
For system data, please refer to the following user manual:
VersaPoint
Automation terminals of the VersaPoint product range GFK-2736
10.1.2
VersaSafe system
VersaSafe system
Shutdown time t
OUT_LPSDO
15ms
Maximum number of VersaSafe islands in the system
Maximum number of VersaSafe islands in
the system 31
Maximum number of modules within a VersaSafe island 1 IC220SDL963
16 satellites (IC220SDLxx, freely mixed)
Memory capacity
30 kB for safety logic
10.2
IC220SDL963
General data
Housing dimensions (width x height x
depth)
48.8 x 119.8 x 71.5 mm
Weight (with connectors)
200 g
Operating mode
IC220SDL963
Process data mode with 24 words
Transmission speed (local bus)
500 kbaud or 2 Mbaud
Ambient temperature
Operation
-25°C to +55°C
Storage/transport
-25°C to +70°C
Humidity
Operation
75% on average, 85% occasionally (no condensation)
Important
In the range from -25°C to +55°C appropriate measures against increased humidity
must be taken.
Storage/transport
75% on average; 85% occasionally (no condensation)
Important
For a short period, slight condensation may appear on the outside of the housing.