Earthing and shielding
420
Figure 253: Shielding using Gas Discharge Tubes
7.2
Potential Ratios
7.2.1
Basic Aspects
Concerning the potential ratios of a RSTi-EP system, the following aspects must be kept in
mind:
•
The power supply of the network adapter and I/O modules as well as field power is
provided via the power supply at the power-feed module (PF)
•
A potential-free design is made possible using an isolated power supply at the system
power supply and the field power supply
The block diagram shows the typical design of a RSTi-EP system. The power supply concept
here makes sure that, starting with a certain capacity utilization, power refresh is
implemented using power-feed modules.
Figure 254: RSTi-EP Power Supply Concept
7.2.2
Potential-Free Design
In a potential-free design, the reference potentials of control and load circuits are
galvanically isolated from each other. A potential-free design is necessary for the following:
—
Use of the power-feed module (EP-19xx), i.e. in all AC load circuits