![Emerson PACSystems RSTi-EP User Manual Download Page 380](http://html.mh-extra.com/html/emerson/pacsystems-rsti-ep/pacsystems-rsti-ep_user-manual_101460380.webp)
User Manual
Section 5
GFK-2958L
May 2021
Detailed Description of I/O Modules
366
Measurement
Range
Value in °C
0.1° resolution
Value in °F
0.1°/digit
Value in °K
0.1°K/digit
Range
-40
248
2,692
Underloading
23,190
32,767
25,922
Overloading
32,767
32,767
32,767
Line break,
cold compensation error
5.33.8
Process Alarm EP-3804
Name
Number of bytes
Function
High alarm
1
Bit 0: Upper limit exceeded channel 0
Bit 1: Upper limit exceeded channel 1
Bit 2: Upper limit exceeded channel 2
Bit 3: Upper limit exceeded channel 3
Bit 4
–
7: Reserved
Low alarm
1
Bit 0: Lower limit exceeded channel 0
Bit 1: Lower limit exceeded channel 1
Bit 2: Lower limit exceeded channel 2
Bit 3: Lower limit exceeded channel 3
Bit 4
–
7: Reserved
Timestamp
2
The two least significant bytes of the internal 32-bit timer