User Manual
Section 4
GFK-2958L
May 2021
Detailed Descriptions of the Fieldbus Network Adapters
64
Specification
Description
Conductor cross-section
Single-wired, fine-wired
0.14
–
1.5 mm2 (AWG 16
–
26)
Weight
Operating temperature
-20°C to +60°C (-4 °F to +140 °F)
Storage temperature
-40°C to +85°C (-40 °F to +185 °F)
Air humidity (operation/transport)
5% to 95%, noncondensing as per DIN EN 61131-2
Width
52 mm (2.05 in)
Depth
76 mm (2.99 in)
Height
120 mm (4.72 in)
Weight
223 g (7.87 oz)
Configuration
The GSD file is available on the Support website
https://www.emerson.com/Industrial-Automation-
Controls/support
for download and import into PAC
Machine Edition. The GSD supporting a firmware
release is part of the firmware upgrade kit, also available
on the Support website.
General data: refer to Section 1.3, General Technical Data for the Fieldbus Network Adapter.
4.1.5
Modifiable Parameters EPXPBS001
Parameter
Additional explanations
Optional values
Default
IP address USB port
†
192.168.1.202; 192.168.2.202,
192.168.3.202, 192.168.4.202,
192.168.5.202
192.168.1.202
DP-Alarm mode
V0 / V1
V1
DP alarm mode V0
For mode V0, the alarm triggers are set in the parameter data.
Diagnostic alarm
These switches are always
selectable, but they only have a
function in mode V0. Diagnostic
messages are generated which
are not acknowledged by the
PLC.
enabled / disabled
disabled
Process alarm
enabled / disabled
disabled
Hot-plug alarm
enabled / disabled
enabled
DP alarm mode V1
In mode V1, the alarm triggers are set in the engineering environment.
Diagnostic alarm
These switches can be selected
only in mode V1, in V0 they are
inactive. Diagnostic messages
are
generated
which
are
acknowledged by the PLC.
enabled / disabled
disabled
Process alarm
enabled / disabled
disabled
Hot-plug alarm
enabled / disabled
enabled
Identifier-related diagnosis
A diagnostic block is attached to
the diagnostic message.
enabled / disabled
enabled
Channel-related diagnosis
A diagnostic block is attached to
the diagnostic message.
enabled / disabled
enabled
Module status
A diagnostic block is attached to
the diagnostic message.
enabled / disabled
enabled
Data format
Motorola / Intel
Motorola