Detailed Description of I/O Modules
209
5.16.3
Modifiable Parameters for EP-5111
Channel
Description
Options
Default
Diagnostic alarm
disabled (0) / enabled (1)
disabled
0
Filter time signal A
0.01ms [100 kHz] (0) /
0.017ms [50 kHz] (1) /
0.033ms [30 kHz] (2) /
0.1ms [10 kHz] (3) /
0.2ms [5 kHz] (4) /
0.5ms [2 kHz] (5) /
1ms [1 kHz] (6)
0.01ms
0
Filter time signal B
0.01ms [100 kHz] (0) /
0.017ms [50 kHz] (1) /
0.033ms [30 kHz] (2) /
0.1ms [10 kHz] (3) /
0.2ms [5 kHz] (4) /
0.5ms [2 kHz] (5) /
1ms [1 kHz] (6)
0.01ms
0
Filter time latch
0.01ms (0) /
0.017ms (1) /
0.033ms (2) /
0.1ms (3) /
0.2ms (4) /
0.5ms (5) /
1ms (6)
0.01ms
0
Filter time gate
0.01ms (0) /
0.017ms (1) /
0.033ms (2) /
0.1ms (3) /
0.2ms (4) /
0.5ms (5) /
1ms (6)
0.01ms
0
Filter time reset
0.01ms (0) /
0.017ms (1) /
0.033ms (2) /
0.1ms (3) /
0.2ms (4) /
0.5ms (5) /
1ms (6)
0.01ms
0
Process alarm HW gate open
disabled (0) / enabled (1)
disabled
0
Process alarm HW gate closed
disabled (0) / enabled (1)
disabled
0
Process alarm overflow
disabled (0) / enabled (1)
disabled
0
Process alarm underflow
disabled (0) / enabled (1)
disabled
0
Process alarm comp. value
disabled (0) / enabled (1)
disabled
0
Process alarm end value
disabled (0) / enabled (1)
disabled
0
Process alarm latch value
disabled (0) / enabled (1)
disabled