29
3.5.1
Power Supply Derating
The power supply is restricted according to the temperature. The following values apply for
the horizontal and vertical positioning of the RSTi-EP station:
Temperature-dependent Values for the Power Supply
Power Source
Horizontal
Vertical
Network Adapter power supply
60 °C / 140 °F: 2 x 8 A
55 °C / 131 °F: 2 x 10 A
55 °C / 131 °F: 2 x 6 A
50 °C / 122 °F: 2 x 8 A
Power-feed module power
supply
60 °C / 140 °F: 1 x 10 A
55 °C / 131 °F: 1 x 8 A
Current Demand
Product group
Product
I
SYS
I
IN
I
OUT
I
S
I
L
Network adapters
EPXPBS001
100 mA
EPXPNS001
116 mA
EPXPNS101
116 mA
EPXETC001
110 mA
EPXMBE001
112 mA
EPXMBE101
112 mA
EPXEIP001
112 mA
Digital input modules
EP-1214
8 mA
18 mA
x
EP-1218
8 mA
30 mA
x
EP-1318
8 mA
30 mA
x
EP-125F
8 mA
52 mA
EP-12F4
8 mA
18 mA
x
EP-1804
8 mA
EP-153F
8 mA
52 mA
x
Digital output modules
EP-2214, EP-2714, EP-2634
8 mA
20
mA
x
EP-2218
8 mA
35
mA
x
EP-225F, EP-2614
8 mA
25
mA
x
EP-2814
11 mA
EP-291F
8mA
30mA
x
Analog input modules
EP-3164, EP-3124, EP-3264
8 mA
25 mA
x
EP-3664
8 mA
31 mA
+Load
EP-3804, EP-3704, EP-3368,
EP-3468
8 mA
20 mA
EP-1813
8 mA
≤
40
mA
Analog output modules EP-4164, EP-4264
8 mA
85
mA
Functional modules
EP-5111, EP-5112
8 mA
35 mA
x
EP-5212
8 mA
35 mA
x
x