User Manual
Section 13
GFK-2958L
May 2021
IO-Link Device Configuration
511
Observe the manufacturer ‘s documentation.
13.4.5
Determining the process data length
You can determine the process data length that is required for the IO-Link device
configuration.
Figure 354: Determining the process data length
➢
Navigate to the IO-Link port overview.
➢
Read the process data length of the current configuration.
−
PD IN: Length of the input data in bytes
−
PD OUT: Length of the output data in bytes
13.4.6
Finding & rectifying parameter errors
Faulty parameterized IO-Link devices are indicated by a red frame around the IO-Link port
concerned.
Figure 355: Faulty parameterized IO-Link device
➢
Open the detailed view of the IO-Link device.
Figure 356: Jumping to faulty parameter value
➢
Click Scroll to error in order to jump to the next faulty parameter entry.
The faulty entry is indicated by a red frame. A note regarding error diagnosis is displayed.