User Manual
Section 6
GFK-2958L
May 2021
Installation
407
6.2
Assembling the RSTi-EP Station
WARNING
Explosion risk - During assembly work, sparks can form, and surfaces may become
excessively hot.
•
Before assembly, make sure that there is not a potentially explosive atmosphere.
•
For applications in potentially explosive atmospheres, observe the installation and
construction requirements of EN 60079- 15 and/or country-specific regulations
DANGER
Dangerous contact voltage:
•
Carry out assembly and wiring work on the RSTi-EP station only when the power supply
is disconnected.
•
Make sure that the place of installation (switch cabinet etc.) has been disconnected
from the power supply.
CAUTION
The product can be destroyed by electrostatic discharge.
•
The components in the RSTi-EP series can be destroyed by electrostatic discharge.
•
Ensure that personnel and work equipment are adequately grounded.
Note
:
For failure-free operation, the end brackets delivered with the network adapter must
be installed to achieve a permanent set of the RSTi-EP station.
1.
On the left side of the installation site, place an end bracket on the DIN rail with the
exterior of the bracket facing left and screw it down tightly (using a 3-
mm (0.1”)
screwdriver).