User Manual
Section 5
GFK-2958L
May 2021
Detailed Description of I/O Modules
177
5.9.2
Specifications EP-2614
Specification
Description
System data
Data
Process, parameter and diagnostic data depend on the
network adapter used (refer to Section, Order and
Arrangement of Modules).
Interface
RSTi-EP I/O communication bus
System bus transfer rate
48 Mbps
Outputs
Number
4
Type of load
ohmic, inductive, lamp load
Response time
low » high max. 100
μ
s; high » low max. 250
μ
s
Max. output current
per channel
2 A
per module
8 A
Breaking energy (inductive)
150 mJ per channel
Switching frequency
Resistive load (min.
47Ω)
1 kHz
Inductive load (DC 13)
0.2 Hz without free-wheeling
diode
1 kHz with suitable free-
wheeling diode
Lamp load (12 W)
1 kHz
Actuator connection
2-wire, 3-wire, 3-wire + FE
Actuator supply
max. 2 A per plug, total max. 8 A
Short-circuit-proof
Yes
Protective circuit
Constant current with thermal switch-off and
automatic restart
Response time of the current limiting circuit
< 100
μ
s
Module diagnosis
Yes
Individual channel diagnosis
No
Can be used with EP-19xx
Yes
Supply
Supply voltage
20.4V
–
28.8V
Current consumption from system current path ISYS
8 mA
Current consumption from output current path IOUT
25 mA + load
General data
Weight
86 g (3.03 oz)
For additional general data, refer to Section,
General Technical Data for I/O Modules