User Manual
Section 5
GFK-2958L
May 2021
Detailed Description of I/O Modules
262
5.19.3
Modifiable Parameters for EP-5261
Description
Options
5
Default
Operating mode
Disabled (0) /
RS232 (1) /
RS485 (2) /
RS422 (3)
Disabled
Data bits
6
7 Bit (0) / 8 Bit (1)
8 Bit
Baud rate
300 (0) /
600 (1) /
1200 (2) /
2400 (3) /
4800 (4) /
9600 (5) /
14400 (6) /
19200 (7) /
28800 (8) /
38400 (9) /
57600 (10) /
115200 (11)
9600
Stop bit
1 Bit (0) / 2 Bit (1)
1 Bit
Parity
None (0) /
Even (1) /
Odd (2)
None
Flow control
None (0) /
CTS/RTS (1) /
XON/XOFF (2)
None
XON character
0 ... 255
17
XOFF character
0 ... 255
19
Terminating resistor
RS485/422
Off (0) / On (1)
Off
Process data length
16 Byte (1)
16 Byte
5.19.4
Diagnostic Data EP-5261
Name
Bytes
Bit
Description
Default
Error indicator
0
0
Module error
1
Internal error
2
External error
3
Channel error
0
4
Error
5
Reserved
0
6
Reserved
0
7
Parameter error
Module type
1
0
Module Type 0x05
1
1
0
2
1
5
Values in brackets for EtherCAT and Modbus-TCP.
6
The option “7 Bit“ works only in combination with a parity ("even" or "odd").