User Manual
Section 4
GFK-2958L
May 2021
Detailed Descriptions of the Fieldbus Network Adapters
73
4.2.4
Modifiable Parameters: EPXPNS001/EPXPNS101
Parameter
Optional values
Default
IP address
†
4 numbers between 0 and 255
Subnet mask
4 numbers between 0 and 255
Gateway
4 numbers between 0 and 255
Webserver via Ethernet
disabled / enabled
disabled
IP address USB port
192.168.1.202; 192.168.2.202,
192.168.3.202, 192.168.4.202,
192.168.5.202
192.168.1.202
Process alarm
disabled / enabled
disabled
Diagnostic alarm
disabled / enabled
disabled
Type of diagnostic
Extended channel diagnostic (short
diagnostic)
Manufacturer-specific diagnostic (complete
diagnostic)
Extended channel diagnostic
(short diagnostic)
Behavior of outputs on fieldbus
errors
All outputs off /
Enable substitute value /
Hold last value
All outputs off
Module behavior on hot swap
Continue data exchange /
Behavior like fieldbus error
Continue data exchange
Data format
Motorola / Intel
Motorola
Lock force mode
Force mode unlocked /
Force mode locked
Force mode unlocked
Option Handling
@
disabled / enabled
disabled
Group Module Diagnostic Alarm
@
disabled / enabled
disabled
Reduce Return of Submodule
Alarm
@
disabled / enabled
disabled
†
Change requires restart of the network adapter.
@
These parameters added from revisions: EPXPNS001-ABAE and EPXPNS101-AAAA.