5 | ZincBlue2 User Manual
Warnings and Cautions
UPS
Battery Panel / Module
To avoid fire, shock, or death; turn off power at circuit breaker or fuse and test that power is off before wiring,
servicing, or removing.
Read this manual prior to installation and operation. If you have any questions about safe installation, operation or
maintenance, contact ZincFive’s Support Department.
Carefully unpack the components. Report any shipping or other damage at once.
Never let live battery wires touch the UPS, the enclosure, or any other metal objects.
Use proper lifting techniques when lifting or moving the UPS or its components.
At high ambient temperature conditions, the UPS’ surface can be very hot to the touch when operating.
Ensure ventilation to the left and right sides of the UPS enclosure.
To be installed and/or used in accordance with electrical codes and regulations.
Before installation, verify the input voltage and current requirements of the load are met by the UPS’ output. Verify
the line voltage and current meet the UPS input requirements.
To avoid electric overload, do not exceed output rating.
UPS Input & Output Values
Battery installation and servicing should be done or supervised by personnel knowledgeable about
batteries and the required precautions.
Battery Panel / Module must not be installed in a sealed enclosure, ventilation must be provided.
Use proper lifting techniques when lifting or moving the batteries.
Never dispose of batteries in a fire.
Never open or damage the batteries.
A battery can present a risk of electrical shock and high short-circuit current. The following precautions should
be observed when working on batteries:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Disconnect the AC input to the Battery prior to connecting or disconnecting battery terminals.
Ensure that the Battery is OFF before connecting or disconnecting battery interconnect cables. The
Battery Panel / Module indicator LED will be OFF.
Never short pins inside battery cable connectors.
Input Voltage Range
120Vac Nominal
85-140Vac User Programable
Input Current
15A max
Input Frequency
60Hz nominal
+/-10% (54 - 66Hz)
Output Voltage
/-3%
Output Current
8.3A Typical
Output Power
1,000VA Typical
Output Frequency
60Hz +/-0.5Hz
Output Waveform
Pure Sinewave
UPS Efficiency
0.97
ZincBlue2 UPS 1000W operating temperature range
-37°C to 74°C (-34°F to 165°F)
ZincBlue2 UPS 1000W
UL 1778 and CSA C22.2 No. 107.3 compliant in a maximum ambient environment of 40°C
Input Power
Environmental
Output
Regulatory Compliance