Parameter List and Menu Structure of VS 300
135
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
No. of compressor stages
Default No. of compressor
stages at HP fault
1 - 2
1
3 - 5
2
6 - 7
3
8 - 10
4
11 - 12
5
S
Menu 3-5 Inputs
INPUTS
POS: XXXXX
1 INPUT 1
Next: Screen 3-5-1
2 INPUT 2
Next: Screen 3-5-2
3 INPUT 3
Next: Screen 3-5-3
4 INPUT 4
Next: Screen 3-5-4
S
Menu 3-5-1 INPUT 1
INPUT 1
POS: XXXXX
Entry
Default
NT
LT
HP
Dim.
Time delay
XX s
External alarm delay in seconds
0 - 60
0
0
0
s
Alarm message:
XXXXXXXXXXXXXXXXXXXXXXXXX
Text displayed on occurrence of external
alarm (through digital input 1): Default
Ext. Alarm I1
Text
-
-
-
-
Function: ExtAlarm
→
Function performed when digital input 1 is
activated
Screen 3-5-1-a
linked to:
→
Enter control loop to receive function in
itiated through digital input 1
Screen 3-5-1-b
Polarity
X
Polarity of digital input 1
0: Low active (activated at signal voltage
0/cable break)
1: High active (activated at signal voltage
= 230 V AC)
0 - 1
0
0
0
-
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...