Parameter List and Menu Structure of VS 300
124
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
S
Menu 3-1 System Configuration (CL2)
CONFIG
POS: XXXXX
Entry
Default
NT
LT
HP
Dim.
No. Comp./Cond CL2
XX
Number of compressors/fans (base load
stages) in CL2
With step control:
With speed control:
With combined control:
0 - max.
1)
1 or 2
min. 2-max.
1
)
2/4/6
1)
2/4/6
1)
2/4/6
1)
-
Cap.Stages
CL2
XX
Number of capacity stages each capacity-
controlled base load stage CL2
With step control:
With speed control:
With combined control:
1 - 3
1)
= 1
= 1
1
1
1
-
No.multist.
CL2
XX
Number of capacity-controlled base load
stages CL2
With step control:
With speed control:
With combined control:
0 - max.
1)
= 0
= 0
0
0
0
-
Enable
CL2
-stages
→
Enable/disable control stages in CL2
→
See Screen 3-1-e
Stg.Ld.Shed. CL2
X
Number of disabled relay/control stages
on load shedding CL2
0 - 3
0
0
0
-
Refrig.
CL2
XXXXX
→
Select refrigerant in Control Loop 2
→
See Screen 3-1-f
TRANSD.
CL2
→
Sensor matching Control Loop 2
→
See Screen 3-1-g
Enab. tr CL2
Activate room/outside temperature analy
sis CL2 (only available with CAN Bus)
↑
,
↓
,
(ON/OFF)
OFF
OFF
OFF
-
Enab.Humid.CL2
Activate analysis of air humidity
↑
,
↓
,
(ON/OFF)
OFF
OFF
OFF
-
Node-Nr Env.CL2
CAN Bus node number of the VS
3000/VS 3000 BS from which CL2 draws
ambient data (humidity, outside/room
temperature)
1..9
-
-
-
-
to-MinMon CL2
Activation of compressor shutdown by
shortfall relative to min. temperature CL1
(only LP control)
2) 4)
↑
,
↓
,
(ON/OFF)
ON
ON
-
-
tc-MaxMon CL2
Activation of compressor shutdown by
shortfall relative to max. temperature CL2
(only HP control)
2)
↑
,
↓
,
(ON/OFF)
-
-
OFF
-
Conumer.cont.
CL2
→
Select control by refrigeration point or
suction pressure Control Loop 2
3)
→
See Screen 3-1-h
Cons.nodeNo.
CL2
Enter refrigeration point to control 2nd
control loop of pack
1 - 99 or ---
--
--
--
-
forced ret.
CL
2
X
Select oil equalization function Control
Loop 2
3)
↑
,
↓
, (N/Y)
N
N
-
-
Max. Off Time
XXXm
Enter maximum allowed run time before
forced shutdown
2)
.
Only shown when forced shutdown func
tion activated.
60..180
180
180
-
min
Off Time
XXXm
Enter standstill time after forced shut
down
2)
.
Only shown when forced shutdown func
tion activated.
1..5
2
2
-
min
No.AlRelays
XXXX
Number internal alarm relay
0..1
0
0
0
-
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...