Parameter List and Menu Structure of VS 300
106
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
CL1
CL2
Function/
Description
Range
Default
Dim.
Displayed / Condition
(1): Minimum of one stage must
be defined in CL:
CL1:
S301
>
0
CL2:
S331
>
0
NT
LT
HP
S304.1..
S304.12
S334.11.
.
S334.12
Enable/disable relay/
control stage 1 - 12
1)
0: Disabled
1: Enabled
1
1
1
-
(1)
S305
S335
Number of disabled
relays on load shed
ding
0..3
0
0
0
-
S306
S336
Enter refrigerant
For details see 3)
3
3
3
-
S308
S338
Set pressure trans
mitter parameter:
Pressure at 4 mA
0,0..2,0
0,0
0,0
1,0
bar
S309
S339
Set pressure trans
mitter parameter:
Pressure at 20 mA
8,0..60,0
10,0
10,0
26,0
bar
S310
S340
Enable temperature
shift
0: Disabled
1: Enabled
0
0
0
-
S311
S341
Enable humidity shift
0
0
0
-
S312
S342
CAN Bus node
number for ambient
data CL#
1..9 or disabled
---
---
---
-
-
S343
Enable max. tempe
rature disable CL2
0: Disabled
1: Enabled
0
0
0
-
(1) and
CL1 must be LP controller and
CL2 must be HP controller
(see S390)
S314
S344
Enable min. tempe
rature disable
CL1/CL2
1
1
-
-
Respective CL must not be HP
controller
S315
S345
Refrigeration point
control
0: Control by suction
pressure
1: Control by refrigeration
point
0
0
-
-
S316
S346
Refrigeration point
CAN Node No.
1 - 99 or disabled
---
---
-
-
S317
S347
Forced shutdown/
Activate oil equaliza
tion function
0: Not activated
1: Activated
0
0
-
-
S318
S348
Maximum run time
60...180
180
180
-
min
Respective CL must not be HP
controller
Forced shutdown must be acti
vated in CL
S319
S349
Standstill time
1...5
2
2
-
min
1)
Maximum values varying with expansion stage/Number of relay stages can be 4/8/12
2)
Dependent on expansion stage/number of relay stages
3)
Refrigerant: 0=R22, 1=R502, 2=R134a, 3=R404A, 4=R402
A
, 5=R717, 6=R1270, 7=R507, 8=R407
C
,
9=R410
A
, 10=R290, 11=R744, 12=R407F, 13=R422A, 14=R422D, 15=R408A, 16=R407D, 17=R407A,
18=R427A, 19=R438A, 20=R152a, 21=R170, 22=R600, 23=R600a, 24=R449A, 25=R450A, 26=R448A,
27=R455A, 28=R447B, 29=R1234ze, 30=R1233zd, 31=R1234yf
Parameter List S3:
To change values set access level to
setpoint adjustment enabled
(Parameter A060=1, see section 7.7 Changing the Access Level).
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...