Parameter List and Menu Structure of VS 300
107
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
8.1.9
Parameter List S3: Common Setpoints System Configuration
Parameter No.
Function /
Description
Range
Default
Dim.
Displayed /
Condition
I1
I2
I3
I4
NT
LT
HP
S360
S364
S368
S372
Function of digital input
1 - 4
0: Off
1: Fast unload
2: Load shedding
3: Setpoint toggle
4: Alarm recording
5: HR mode
6: Safety loop
4
4
4
-
Always shown
S361
S365
Allocation of digital in
put 1 - 4
0: CL1
1: CL2
2: Both control loops
0
0
0
-
(1)
S369
S373
1
1
1
S362
S366
S370
S374
Polarity of digital input
1 - 4
0: Low active
1: High active
0
0
0
-
Always shown
S363
S367
S371
S375
Alarm delay for digital
input 1 - 4
0 - 60
0
0
0
s
S376
Number internal alarm
relay
0..2 *
0
0
0
-
S377
Booster operation:
Shutdown disable CL2
when compressor in
CL
0: NOT disabled
1: Disabled
0
0
-
-
(1) and neither CL1 or
CL2 are permitted to
be HP controllers
I1 to I4:
Digital inputs 1 - 4
(1): Minimum of one stage must be defined in CL:
CL1:
S301
> 0
CL2:
S331
> 0
Parameter List S3:
To change values set access level to
setpoint adjustment enabled
(Parameter A060=1, see section 7.7 Changing the Access Level).
* Maximum value, depends on VS 300 system / number of alarm ralais: 4/8/12!
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...