Parameter List and Menu Structure of VS 300
125
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
SperrRK2 m. RK1
XXX
Booster operation: disable shutdown CL2,
when compressor running in CL2 (only
shown in Superuser mode)
↑
,
↓
,
(ON/OFF)
OFF
OFF
-
-
Config
XXXX
Controller configuration (NT/LT/HP)
(only configuarble in terminal mode and
Superuser mode)
→
See Screen 3-1-i
1)
0 to 4/8/12 depending on expansion stage and configuration
(see section 3 Function - System Configuration/Allocation of Relay/Control Stages).
2)
CL1 must not be HP controller.
3)
CL2 must not be HP controller.
4)
CL2 must be HP controller.
S
Screen 3-1-a CL1 Compressors/Fans: Enable/Disable Control Stages
CL1-Comp/COND
POS: XXXXX
Entry
Default
NT
LT
HP
Dim.
Stage 1
1)
XXX
Shows only relay/control stages allocated
to Control Loop 1
↑
,
↓
(ON/OFF)
ON
ON
ON
-
...
Stage 12
1)
XXX
1)
0 to 4/8/12 depending on expansion stage and configuration (see section 3 Function - System
Configuration/Allocation of Relay/Control Stages).
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...